A. Introduction

Pursuant to Title 30, Texas Administrative Code, Section 290.44, it is the responsibility of the City of Fort Worth to protect its drinking water supply by instituting and enforcing a cross connection program.  The program includes the installation of backflow prevention assemblies where deemed appropriate or necessary.

It is a logical assumption that because water is always under pressure, it can only flow in one direction.  However, it is possible for the flow to be reversed.  Water will always flow towards the point of lowest pressure.  If a main line in our system should break, or if a fire occurred and the fire department opened several hydrants, the pressure in our water mains could drop dramatically, causing a reversal of flow.  The potential for this reversal of flow is why our department is concerned about the possibility of backflow of contaminants into our water system.

Key definitions

  • CROSS CONNECTION is any physical arrangement where a public water system, such as the City of Fort Worth, is connected directly or indirectly with any other apparatus that may cause any substance, other than the city's drinking water, to enter the drinking water system.
  • BACKFLOW means the flow in the direction opposite to the normal flow or the introduction of any foreign liquids, gases, or substances into the water distribution system.

Some cross connections are necessary and cannot be eliminated.  Therefore, appropriate isolation methods and assemblies must be employed to protect against the potential of a backflow incident.   

B. Applicability

As a condition of water service, all customers shall install, maintain, and operate their piping and plumbing systems in accordance with the City’s Plumbing Code and its Environmental Protection and Compliance Ordinance #12274.  If there is a conflict between this guidance document and these codes, the more restrictive provision shall apply.     

 

C. Circumstances Requiring Use of Backflow Assemblies

At a minimum, a backflow prevention assembly will be required in each of the following circumstances:

  1. When the nature and extent of any activity at a premise, or the materials used in connection with any activity at a premise, or materials stored at a premise, could contaminate or pollute the potable water supply.
  2. When a premises has one or more cross connectionsare not correctable.
  3. When intricate plumbing arrangements are present that make it impractical to ascertain whether cross connections exist.
  4. When a premises has a repeated history of cross connections being established or re-established.
  5. When entry to a premise is unduly restricted so that inspections for cross connections cannot be made with sufficient frequency to assure that cross connections do not exist.
  6. When materials are being used such that, if backflow should occur, a health hazard could result.
  7. When installation of an approved backflow prevention assembly is deemed by an Inspector to be necessary to accomplish the purpose of these regulations.
  8. When an appropriate cross connection survey report form has not been filed with the Director.
  9. When a fire sprinkler system using non-potable piping material is connected to the City's water system.
  10. In all new nonresidential construction there shall be installed an approved backflow assembly at the service connection. The type of the assembly will be commensurate with the degree of hazard as determined by an Inspector.
  11. If apremisesis required to have backflow prevention assemblies, but water cannot be turned off during the testing of such assemblies, the premises shall be equipped with dual backflow prevention assemblies of the same type so that testing, repair and maintenance can be performed
  12. Any used water return system that has received approval from the Director.
  13. If a point-of-use assembly has not been tested or repaired as required by this Division, a premise isolation assembly shall be required.
  14. If a Backflow or Plumbing Inspector determines that additions or rearrangements have been made to the plumbing system without the proper permits as required by the Plumbing Code, premise isolation shall be required.
  15. All multistory buildings or any building with a booster pump or elevated storage tank.
  16. Retrofitting shall be required on all health hazard connections and wherever else the Director deems retrofitting necessary. (No “Grand fathering” for health hazards – ever.)
  17. Interconnectbetween any of the buildings on the premises.    

top

D.  Installation Specifications

Backflow prevention assemblies shall be installed in accordance with the Plumbing Code and this Division.  The assembly installer shall obtain the required plumbing permits prior to installation and shall have the assembly inspected by a certified cross connection inspector and as required by the Plumbing Code.  

  1. No part of a reduced pressure principle backflow prevention assembly shall be submerged in water or installed in a location subject to flooding.  All assemblies installed below grade shall have non-ferrous threaded plugs inserted in the test ports.
  2. Assemblies shall be installed at the point of delivery of the water supply, before any branch in the line, and on private property located just inside the boundary of the City's right-of-way.  An Inspector may specify other areas for installation of the assembly. The assembly shall be protected from freezing and other severe weather conditions.
  3. All vertical installations shall be approved, in writing, prior to installation and all vertical installations must be of an assembly approved by USCFCCCHR.
  4. The assembly shall be readily accessible with adequate room for maintenance and testing.  Assemblies two (2) inches and smaller shall have at least a six (6)-inch clearance on all sides of the assembly.  All assemblies larger than two (2) inches shall have a minimum clearance of twelve (12) inches on the back side, twenty-four (24) inches on the test cock side, twelve (12) inches below the assembly and thirty-six (36) inches above the asse mbly.
  5. If the Director grants written permission to install the backflow assembly inside of a building, the assembly shall be readily accessible between 8:00 a.m. and 5:00 p.m., Monday through Friday.
  6. If an assembly is installed pursuant to Ordinance 12274 12.5-531, subsection (a)(8), and is four (4) inches or larger and is installed five (5) feet or higher above the floor, it shall be equipped with a rigidly and permanently installed scaffolding acceptable to the Director.  This installation shall also meet all applicable requirements set out by the U.S. Occupational Safety and Health Administration and the State of Texas occupational safety and health laws.
  7. RP assemblies may be installed in a vault only if relief valve discharge can be drained to daylight through a bore sight type drain.  The drain shall be of adequate capacity to carry the full rated flow of the assembly and shall be screened on both ends.
  8. An approved air gap shall be located at the relief valve orifice of RP assemblies.  This air gap shall be at least twice the inside diameter of the incoming supply line as measured vertically above the top rim of the drain and in no case less than one (1) inch.
  9. All assemblies installed in a vault that is 5 ft. from finish floor to top of lid must have a permanently installed ladder.

 

Table D-1, Required  -Point of Use (Internal) Protection Systems

Aspirator (medical)

 Health

 Bedpan Washers

 Health

 Autoclaves   

 Health

 Specimen tanks

 Health

 Sterilizers

 Health

 Cuspidors

 Health

 Lab Bench equipment

 Health

 Autopsy and mortuary equipment

 Health

 Sewage pump

 Health

 Sewage ejectors

 Health

 Fire-fighting system w/chemical introduction

 Health

 Connection to sewer pipe

 Health

 Connection to plating tanks

 Health

 Irrigation systems with chemical additives or agents

 Health

 Connection to salt-water cooling system

 Health

 Tanks, vats or other vessels containing toxic substances

 Health

 Connection to industrial fluid systems

 Health

 Dye vats or machines

 Health

 Cooling towers with chemical additives

 Health

 Trap primer

 Health

 Steam generators

 Health

 Heating equipment Commercial or Domestic

 Health

 Irrigation systems (no chemical injection)

 Non-health

 Swimming pools Public or Private

 Health

 Carbonated Drink Dispensers w/pump

 Health

 Ornamental fountains

 Health

 Degreasing equipment

 Non-health

 Lab bench equipment

 Non-health

 Hose bibs

 Non-health

 Trap primers

 Non-health

 Flexible shower heads

 Non-health

 Steam tables

 Non-health

 Washing equipment

 Non-health

 Shampoo basins

 Non-health

 Kitchen equipment

 Non-health

 Aspirators

 Non-health

 Domestic space-heating boiler

 Non-health

AVB designations assume no downstream valving and no constant pressure.  All assemblies must be installed according to City of Fort Worth Ordnance (i.e., AVB's and PVBs are for protection against back siphonage only;  AVBs may not be installed under constant pressure or with downstream valves.  AVBs and PVBs must be installed with appropriate clearances above downstream piping [12”for PVBs, 6” for AVBs.)

Table D-2, Required Premises Isolation (Reprinted from AWWA Manual M-14)

 Description of Cross Connection

 Hazard

Recommended Assembly

 All New, Non-residential Construction

 Non-Health

 DC

 Hospitals, mortuaries, clinics, laboratories

 Health

 RPZA

 Plants using radioactive material

 Health

 RPZA

 Petroleum processing or storage facilities

 Health

 RPZA

 Premises where inspection is restricted

 Health

 RPZA

 Sewage treatment plant

 Health

 RPZA

 Sewage lift stations

 Health

 RPZA

 Commercial laundry

 Health

 RPZA

 Plating or chemical plants

 Health

 RPZA

 Docks and dockside facilities

 Health

 RPZA

 Food and beverage processing plants

 Health

 RPZA

 Pleasure-boat marina

 Health

 RPZA

 Tall Buildings (protection against excessive head of water

 Non-Health

 RPZA, DC

 Steam Plants

 Non-Health

 RPZA

 Reclaimed water systems

 Health

 RPZA

Notes:      
AG = Air gap
DC = Double Check Valve Backflow-prevention assembly
AVB = Atmospheric Vacuum Breaker
RPZA = Reduced-pressure principle Backflow prevention-assembly
PVB = Pressure Vacuum Breaker  

top  

E.  Special Considerations

Thermal expansion
It is the responsibility of the property owner to eliminate the possibility of thermal expansion, if a closed system has been created by the installation of a backflow assembly.

Pressure Loss
Any water pressure dropcaused by the installation of a backflow assembly shall not be the responsibility of the City.  The Department may give reasonable assistance to a property owner regarding information on adequate sizing of assemblies and proper plumbing practices to provide for required pressure and flows for fire protection.  

F.  Contact Information

If you have any questions or would like any additional information, please feel free to contact us. 